<span Class='notranslate'>Bussmann </span> Lpj-600sp | 6f381 | Low Peak Fuse, 600 A, 600 V
We are closed from Monday, Dec 23rd and will reopen on Monday, Jan 6th. Any orders received during this time will be processed in the New Year.
BUSSMANN LPJ-600SP Low Peak Fuse, 600 A, 600 V | AE8QTP 6F381

BUSSMANN LPJ-600SP Low Peak Fuse, 600 A, 600 V

Item: AE8QTP Model: LPJ-600SPCross Ref: 6F381
In Stock : 130 Units

Get it by Friday, Dec 27

€398.50 /unit
Add To Cart
Request a Quote

Payment Options Available

Product Specifications:

ItemFuse
Ac Voltage Rating600V
Body MaterialMelamine
Body StyleBlade
ClassClass J
Connection TypeBolted Blade End x Bolted Blade End
Current Rating600A
Dc Voltage Rating300V
DepthNot Applicable
Diameter2 19/32"
ElementDual
For Fuse Block SeriesCH30J, CH60J, J600, JM600, JM601, JM602, JM604, JM606, JP600, JT600, JTN600
Functionally Equal ToFerraz/Gould AJT, Littelfuse JTD
Fuse Amps600
Fuse Block DesignNon Rejection
Indicating / NonindicatingNonindicating
Interrupt Rating100kA at 300V DC, 300kA at 600V AC
Length8"
Mfr. SeriesBussmann LPJ, Littelfuse JTD, Mersen AJT
Product Datasheetbussmann-lpj-600sp.pdf
Rejection / NonrejectionRejection
Response Time10 sec. @ 500%
SpeedTime Delay
TypeTime Delay Current Limiting
Visual IndicationNon Indicating
Voltage Rating600VAC/300VDC
WidthNot Applicable

Shipping Info:

Ship weight (kg) 1.1925
Ship height (cm)6.35
Ship length (cm)20.32
Ship width (cm)6.35
HS code8536100040
Country of OriginMX

Product Details:

Bussmann LPJ-600SP fuse is a Low-Peak fuse designed to blow quickly when an overcurrent occurs. This delay is intentional and ensures that momentary overcurrents that occur during normal operation, such as motor starting currents or short-duration power surges, do not cause the fuse to trip.

Features:

  • Bussmann LPJ-600SP Low-Peak fuse has a dual-element for time-delay and current-limiting functionalities.
  • This fuse has an interrupt rating of 300kAIC at 600VAC to handle high-energy fault currents.
  • It has a response time of 10 seconds at 500% of the rated current allowing for the safe start-up and operation of inrush-heavy equipment without the risk of unnecessary tripping.
  • This Low-Peak fuse delivers consistent 2:1 ampacity ratios for seamless protection and minimised downtime.
  • It has a melamine body to resist heat generated during resisting overcurrents.

Compatible Accessories:

Frequently Asked Questions:

Q. How does a time-delay fuse differ from a standard fuse?

A. A standard fuse responds immediately to overcurrents and will blow if the current exceeds its rating. In contrast, a time-delay fuse intentionally introduces a delay in its response, allowing it to tolerate temporary overcurrents without tripping.

Q. Why are time-delay fuses important?

A. Time-delay fuses help prevent unnecessary disruptions caused by transient overcurrents during normal equipment operation. They strike a balance between protection and functionality, ensuring that essential equipment does not shut down due to harmless spikes in current.

Q. Can time-delay fuses offer the same level of protection as standard fuses?

A. Yes, time-delay fuses provide similar levels of protection against sustained overcurrents as standard fuses.

Q. Is this fuse indicating or non-indicating?

A. It is a non-indicating fuse. However, if you require an indicating fuse with a similar configuration, you can check out Bussmann LPJ-600SPI fuse that has easyID for convenient identification.

Documentation: